Traditions & innovations
Better Energy Solutions

MWM TCG 2020

The MWM gas engines of the TCG 2020 series are perfectly geared to the challenges of a dynamic market environment. With outputs ranging from 1,000kWe – 2,000kWe, the TCG 2020 meets the high requirements of a broad range of applications and guarantee efficiency, reliability, flexibility, and environmental sustainability, together with low lifecycle costs and high profitability.

TCG 2020

For the Highest Ratings in Ecology and Economy

Electrical Output
1,000kWe - 2,000kWe
Engine Layout
12cyl - 16cyl - 20cyl
Download catalog PDF

ABOUT MWM TCG 2020

Gas Engine Features

All Gas Engines
1

More
Profit

The optimised maintenance concept with cylinder units simplifies accessibility and, along with reduction of the number of different parts, minimises the time required for maintenance.

2

Longer
Run Times

Thanks to the extended service intervals, runs up to 200 hours longer per annum than comparable products. The major overhaul is scheduled after 80,000 operating hours

3

Generator Reliability

The particle-free combustion, with pre-chamber spark plugs, extends the service intervals for the exhaust gas heat exchanger and reduces service costs compared to other combustion methods.

4

Optimum
Efficiency

All components relevant for efficiency and power output are monitored by the TEM. The new, upgraded wastegate in particular ensures a more efficient operation with changing conditions.

5

Turbo
Power

The high-pressure turbocharger A140, with an improved wastegate, allows operation with a broader air intake temperature range and up to higher altitudes.

TCG 2020 performance data

NOx <500 mg/Nm3 *

Natural Gas Application V12 & V16
Natural Gas Application V20
Biogas Application V12
Biogas Application V16 & V20
TCG 2020
V12 K (1)
V12 (2)
V16 K
V16 (2)
V16 K
V16 (2)
Engine type
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
Electrical output
1,125kW
1,200kW
1,500kW
1,560kW
1,500kW
1,560kW
Mean effective pressure
17.4 bar
18.6 bar
17.5 bar
18.1 bar
17.5 bar
18.1 bar
Thermal output ± 8%
1,253kW
1,190kW
1,675kW
1,580kW
1,675kW
1,580kW
Electrical efficiency
40.9%
43.6%
40.9%
43.2%
40.9%
43.2%
Thermal efficiency
45.6%
43.3%
45.7%
43.8%
45.7%
43.8%
Overall efficiency
86.5%
86.9%
86.6%
87.0%
86.6%
87.0%
Power to heat ratio **
0.90
1.00
0.89
0.99
0.89
0.99
TCG 2020
V20 (2)
V20 (HE) [2]
Engine type
50 Hz
50 Hz
Electrical output
2,000kW
2,000kW
Mean effective pressure
18.6 bar
18.6 bar
Thermal output ± 8%
1,977kW
1,912kW
Electrical efficiency
43.7%
44.4%
Thermal efficiency
43.2%
42.5%
Overall efficiency
86.9%
86.9%
Power to heat ratio **
1.01
1.01
TCG 2020
V12 (1.0)[2]
V12 (2)
Engine type
50 Hz
50 Hz
Electrical output
1,000kW
1,200kW
Mean effective pressure
15.5 bar
18.6 bar
Thermal output ± 8%
1,037kW
1,194kW
Electrical efficiency
42.6%
43.0%
Thermal efficiency
44.2%
42.8%
Overall efficiency
86.8%
85.8%
Power to heat ratio **
0.97
1.00
TCG 2020
V16 (2)
V20 (2)
Engine type
50 Hz
50 Hz
Electrical output
1,560kW
2,000kW
Mean effective pressure
18.1 bar
18.6 bar
Thermal output ± 8%
1,577kW
2,012kW
Electrical efficiency
42.6%
43.0%
Thermal efficiency
43.1%
43.3%
Overall efficiency
85.7%
86.3%
Power to heat ratio **
1.00
1.00

* With 5% O2 and dry exhaust gas

** The power to heat ratio is calculated by dividing the electrical efficiency by the thermal efficiency. Please remember that this is a theoretical value that may deviate from actually measured values.

Image
Image
Image
Image

Specifications

Dimensions and Weight

TCG 2020 V12 (1.0)[2] V12 K (1) V12 K (1) V12 (2) V16 K V16 (2) V20 (2) V20 (HE) [2]
Engine type 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz
Bore / stroke 170/195mm 170/195mm 170/195mm 170/195mm 170/195mm 170/195mm 170/195mm 170/195mm
Displacement 70.8dm3 70.8dm3 53.1dm3 53.1dm3 70.8dm3 70.8dm3 88.5dm3 88.5dm3
Speed 1500min-1 1500min-1 1500min-1 1500min-1 1500min-1 1500min-1 1500min-1 1500min-1
Mean piston speed 9.8m/s 9.8m/s 9.8m/s 9.8m/s 9.8m/s 9.8m/s 9.8m/s 9.8m/s
Length 4660mm 4660mm 4790mm 4790mm 5430mm 5430mm 6200mm 6200mm
Width 1810mm 1810mm 1810mm 1810mm 1810mm 1810mm 1710mm 1710mm
Height 2210mm 2210mm 2210mm 2210mm 2210mm 2210mm 2190mm 2190mm
Dry weight genset 11200kg 11200kg 11700kg 11700kg 13300kg 13300kg 17900kg 17900kg

Service Intervals

TCG 2020 V12, V16, V20, V12K, V12K1, V16 First service (check valve clearance) * Cylinder head inspection General overhaul
Natural gas 4000 Oh 32000 Oh * 64000 Oh
Purified biogas, landfill gas, and sewage gas 4000 Oh 32000 Oh * 64000 Oh
Unpurified biogas, landfill gas, and sewage gas 2000 Oh 16000 Oh ** 64000 Oh
TCG 2020 V12 (1.0) First service (check valve clearance) * Cylinder head inspection General overhaul
Natural gas 4000 Oh 40000 Oh * 80000 Oh
Purified biogas, landfill gas, and sewage gas 4000 Oh 32000 Oh * 64000 Oh
Unpurified biogas, landfill gas, and sewage gas 2000 Oh 16000 Oh ** 64000 Oh
Oh – Operational Hours, * "at the latest"

RSE & MWM – Partnership for Energy Excellence 

Through our partnership with MWM, RSE delivers cutting-edge modular solutions, ensuring energy independence and efficiency for businesses worldwide.

Contact Sales